COBODLS
Double 240V Motor Drive Controller with two independent limit switch inputs

Features

• For 240Volt Motors
• Independent limit switch inputs for each motor
• Option for receiver plug-in

Application

• Single or Double Gates

 

COBODLS is now Replaced by COBO40


 Click image to enlarge
Download Datasheet

Description
Installation

 

Description

The COBODLS has two independent limit switch inputs enabling each motor (gate) to stop only when it's limit switch is activated. Whereas in other gate controller card the movement stops when either of the limit switch is activated. This feature comes handy when each gate moves a different distance. Even hydraulic doors can be wired to the COBODLS card. Hydraulic doors have overflow fluid limits which requires the COBODLS to disable the electronic limit switches. This is selectable by linking the limit switches. Limit switches are linked as factory defaults.

The COBODLS has a built-in lock control, push button, photocell control, wireless operation with a remote control transmitter, open collector output, LED Output, limit switch connection and 24VAC Output.

Options, Auto Closing, Open Only, Security Closing and Extended Lock Pulse are user selectable using the on board 4-way dip switch. See table below:

Switch on 4-way code switch

ON

OFF

Switch 1

Enables Auto Close

Disables Auto Close

Switch 2

Enables Auto Close and Open Only

Disables Auto Close and Open Only

Switch 3

Enables Auto Close, Security Close and Open Only

Disables Auto Close, Security Close and Open Only

Switch 4

Extended Lock Pulse

Normal Lock Pulse

Switch 1 and 2

Enables Auto Close, Special Security Close and Open Only

Disables Auto Close, Special Security Close and Open Only

Auto Closing
Enabled when switch 1 is on. The AC timer can be adjusted from 3 to approximately 30 seconds by the on board trimpot called AC. Auto Close timer starts when the door is opened and stopped. Input from the Photo Cell terminal will hold-off the closing cycle.

Open Only
Enabled when switch 2 is on. This feature enables the user to open the door/gate but when the door/gate is opening the remote control is disabled and the door will fully opened. Door closes when auto close timer expires.

Security Closing
Enabled when switch 3 is on. The door/gate immediately closes after the photo beam is broken and the vehicle moves away from the photo beam, even if the door/gate is not fully open.

If the door/gate is opening and no vehicle passes through the door/gate then Auto Close will close the door/gate. An Auto Close time of 3 to 30 seconds can be set on the COBODLS board using the trimpot marked AC.

Extended Lock Pulse
Enabled when switch 4 is on. Lock pulse provides a 2 second pulse on opening and closing cycle on a standard 12-volt lock. When extended lock pulse is enabled an additional 2 seconds is provided, bringing the total lock pulse to 4 seconds. This will result in a 4 second closing and opening delay, between motor 1 and 2.

To use the 2 or 4-second pulse feature, a suitable transformer needs to be connected to the COBODLS. This transformer will supply the extra current that will operate the lock. Recommend transformer size is 60VA to 100VA. Also an 8.2 ohms 5-watt power resistor should be connected in parallel with the 270 ohm 2 watt resistor.

Special Security Close
Enabled when switch 1 and 2 are on. Same as Security Close except door does not reverse to open when Photo beam is broken. This is to prevent car-tailing on more secure sites.

Other Features

Pedestrian Access
In opening direction the door/gate can be stopped when it is opening. This allows the user to open the door/gate partially to give pedestrian access.

Red LED
Red OP and CL LED indicate that the motor is running, when the led is on. If motor is not running and either one of the LED's is on check motor wire connections.

Travel Timer (TRV pot)
The travel timer is factory preset to maximum (30 seconds) and should not be adjusted when motors with limit switches are used. When Hydraulic operation, i.e. no limit switches is used, then you will need to adjust the travel timer. Set the travel-timer to stop relays as indicated by red OP and CL led. We recommend approximately 3 seconds after the door/gate is fully opened or closed. The OP or CL led should go off after 3 seconds when door/gate is fully opened or closed.

If an extra 30 seconds travel time is required, switch the one-way switch (S1) next to the TRV trimpot to ‘on'.

Replaceable Fuse
Replaceable 240VAC 5Amp fuse.

Products in the Range

 

Click image to enlarge

Click image to enlarge

 Click image to enlarge

Installation Instructions
Care should be taken not to cross printed circuit board with 240V wires over or under the board. This would induce spikes onto the sensitive circuitry of the printed circuit board.

When COBODLS PCB is used to switch contactors, a VDR (Voltage Dependent Resistor 275V AC) must be connected across the coil of contactor.

Power
Connect 240 VAC to the terminal block marked 240 VAC.

Motors
Motors should be rated for 240 VAC. Each motor should have three wires, i.e. two actives and one neutral. One active is for opening and the other is for closing.

Both motors operate in parallel. However, motor two has a two second delay on closing to allow double gates to overlap.

Motor starting capacitors of 10F are provided depending on manufacture of motor specifications.

LOCK Output
This terminal block outputs a short pulse on opening and closing cycle. This is used for a standard 12V lock. To extend lock pulse, set code switch 4 to the on position.

To use the 2 or 4-second pulse feature, a suitable transformer needs to be connected to the COBODLS. This transformer will supply the extra current that will operate the lock. Recommend transformer size is 60VA to 100VA.

Push Button Input
Push button is a normally open contact. When pressed it will start the opening or closing cycle. This push button should be waterproof for internal and external use. Waterproofing will prevent false activations, which normally occurs due to moisture inside the button. Door or gate can be held open permanently when push button is pressed continuously.

Photo Cell Input
Photo Cell input is normally closed contact. The photocell is used as a safety feature. If the motors are closing and photo beam is broken, motor will stop instantly and then open fully again. Should an object be blocking the motor (i.e. photo cell is broken), closing cycle or auto closing is disabled. A red LED on the controller card labeled as “PC” indicates photo beam is broken. A handy feature when photocell is not near the box.

Antenna
The antenna connection is used to connect an antenna for the plug in FMR-201 or GLR2701SS. The antenna can be a 50 ohms 27 MHz CB-Antenna or piece of approximately 1 meter of wire.

X Output
Terminal block marked “X” has 24 Volt DC outputted whilst the door is moving. This allows you to connect a 24V relay on terminal marked “X” to switch a warning light or horn when the door is moving. X output can source 20mA.

LED Output
If a visual indication of the gate or door status is required at a remote place, a LED can be wired to terminal block marked “LED”. This LED will be on (and stay on) when gate is open and off when gate is closed.

Limit Switches
The limit switches are normally closed. Both limit switch inputs work independently. To use limit switches remove links from the terminal blocks and wire to relevant limit switches. For three wire operation of limit switches, use two outside holes of terminal block and one positive of the limit switch terminal block (see diagram). Low voltage wiring (24V) can be used for the limit switches.

24 Volts Out
This terminal is used to supply an external device that uses 24 VAC. For example, if you want to connect a Loop Detector (LD30) you could use this terminal block to supply power to the Loop Detector.

Remote Control
Remote control is achieved by inserting Elsema’s FMR-201, GLR2701SS or GLR43301SS. Power to the COBODLS printed circuit board should be switched off during the installation of a receiver. The transmitter can be an FMT-301, GLT2701 or GLT43301 respectively.

 


© 2008 Elsema Pty Ltd. All rights reserved.